Balancing the heating system. We equalize the temperature in the rooms

Winter in Russia, as usual, comes unexpectedly, exposing all problems with heating. The most common problem in my practice is the uneven heating of the premises.
Where is the problem?
The lion’s share of heating systems is calculated “the old fashioned way”, according to the principle “100 watts per m2 of heated area”. Boiler manufacturers also confirm the general misconception. So, for example, in the description of a 20 kW boiler it is written that the boiler is capable of heating a room up to 200 m², although this, to put it mildly, is not true. With the same success, you can specify both 10 m² and 400 m².

With this method of choosing the power of heating devices, the real heat losses of each room are not taken into account, and they are very far from the average values. Yes, and the average values, with modern requirements for insulation, range from 16 to 40 watts per m2, 100 watts per square meter (approximately) were lost by old Soviet buildings, most of which are already insulated. But this is also the “average temperature in the hospital”, and in reality, corner rooms with a comparable area lose more heat through two street walls, rooms with panoramic windows also require more heat per unit area than rooms with ordinary windows.

As a result, in 8 out of 10 houses we have a problem with uneven heating. This is often aggravated by the fact that the radiators are hung on one long circuit, and the temperature of the far radiators is much lower than that of the near ones. Bottom line — the difference in temperature in different rooms can be very noticeable. You either have to put up with the uncomfortable temperature in some rooms, or heat with a margin, opening the windows where it’s hot, releasing heat into the wind, which costs a lot of money.
What to do?

In most cases, balancing the heating system helps. I’ll make a reservation right away that there is a technical term “balancing the heating system”, which means hydraulic balancing of the system, that is, equalizing the pumping of the coolant along the circuits according to the project. I will deliberately use this term, interpreting it somewhat broader.

The general recommendation for tuning and balancing is not to wait for the result immediately and do not adjust according to the on / off principle. Heating is a very inert system; abrupt actions and lack of patience launch this system into self-oscillations; it is impossible to catch the golden mean with this approach. Adjust in small increments and patiently wait for the desired room to respond to adjustment changes, this usually takes from half to two days. Your patience will be rewarded with thermal comfort.


Radiators with a bottom connection, as a rule, have a built-in valve that combines both adjusting and balancing. On it, you can reduce the coefficient of internal resistance of the radiator (KVS) and additionally screw a thermostatic head (thermal head) onto the control valve. For the hottest radiators, we reduce KVS by turning the balancing cock, setting the resistance higher (the lower the number, the lower KVS) than for less hot radiators, thereby redirecting the hot coolant to less heated ones.

On correctly connected sectional radiators, a control valve is usually placed on the supply line under the thermal head, and a balancing valve on the return line, which can also be “clamped” on radiators in warmer rooms. On such taps, as a rule, there is no scale and it is convenient to adjust them by unscrewing them by so many turns from the twisted state. How much this “something” is determined experimentally, start with 3–4, then either unscrew or twist one or two turns.


Naturally, a simple installation of the thermal head on the control valve suggests itself, but it is more correct to do this after balancing. Firstly, the thermal head will close the tap in a warmer room only after the room has warmed up to the set temperature, and the heat will go to the less warm room not immediately, but much later. Secondly, when the thermal head closes the tap through which the coolant flows at too high a speed, an unpleasant crack or knock is heard, and this happens periodically. In addition to knocking, at high coolant speeds, radiators are constantly noisy. It is not very comfortable to sleep next to a knocking and noisy battery. The recommended speed of the coolant in the radiator connection is 0.3 m/s; valves with thermal heads are designed to work in just such a flow. The task of balancing is to ensure exactly this flow rate across all radiators.
Spinning what we have
If it is not possible to install a thermal head (the corresponding tap is not mounted), then turn what is. There are various types and types of control valves on the market, and if the valve is already installed, it is a sin not to use it for its intended purpose.



There is one but! A ball valve is generally not considered to be an adjusting valve and should not be used for adjustment: only for full closing or opening without intermediate positions. A long stay of the ball valve in an intermediate position contributes to its jamming and the appearance of defects on the ball mirror, which subsequently lift up and disable the seal.

If there is nothing to turn
If radiators without control valves were used during the installation of the heating system, then you should not despair. Instead of limiting the flow of coolant to radiators in excessively warm rooms, you can easily limit the heat transfer of the radiator. The easiest way is to cover it completely or partially. It is not for nothing that radiators are called “convectors”: this means that the heating device gives off most of the heat through convection — due to the flow of warm air. The air, heating up, expands and rushes up, then moving in a large circle, gradually cools down, becomes heavier and falls down at the opposite wall, then returns to the radiator from below, thus creating a closed convection flow. The share of convection in the total heat transfer of most radiators on the market is very high — at least 60%. These are almost limitless possibilities for regulation. You can reduce the heat transfer of any radiator by simply covering it partially or completely, and in this way equalize the temperature in all rooms of the house.


If just covering it is not too aesthetically pleasing, then suitable pieces of foam rubber, sponges for washing dishes, for example, can be used. They can gently plug the convection channels of the radiator from below, so they will be completely invisible. There is one caveat here: if you need to halve the convection flow, do not close the channels at one half of the radiator completely, it is better to close them through one in order to prevent overheating of one part of the radiator compared to the other.

Important!!!
Convection can only be limited at water heating radiators. In no case do not cover or close the channels in electric convectors, it is very dangerous!
The pump may be one of the reasons
It will not be superfluous to play with the adjustments of the circulation pump, increase the speed if it is impossible to balance the system with cranes or lower it in case of hydraulic noise. Circulation pumps built into heating boilers usually also have flow rate adjustment, the instructions for the boiler say how to change their performance and this is not difficult.


Clean means fast
Be sure to check the coarse filter — “mud”, if one is installed. A clogged filter can greatly slow down the pumping of the coolant, up to a complete stop of circulation.

Applies to everyone
By the way, you need to balance all all heating systems, even very well-calculated ones. The fact is that the market offers radiators and convectors with albeit different, but fixed values of power and hydraulic resistance, which naturally are not equal to the calculated and actual requirements. The heater is selected with rounding up to the nearest nameplate power upwards and almost never fits perfectly.
Warm weather to your home!
Yours sincerely, Pro-heating specialist, dinjaa.